Calculation for Chilled Water Piping (Closed Piping
System) :-
Primary Pump :
Sections
|
Flow
|
Velocity
|
Pipe Size Diameter
|
Friction Loss
|
Suction
Side
|
TR
x 2.4
102x2.4=244.8Gallons/Min
(15.4 Litres/Sec)
|
4
to 7
6
Feet/Sec
(1.82metres/Sec)
|
4
Inch
(101.6mm)
|
2.7
Inches of Water Gauge/100Ft
(22.13
Pascals/Metre)
|
Discharge
Side
|
TR
x 2.4
102x2.4=244.8Gallons/Min
(15.4 Litres/Sec)
|
8-12
10
(3.04metres/Sec)
|
3
Inch
(
72.15mm)
|
10.1
Inches of Water Gauge/100Ft
(82.8)Pascals/Metre)
|
Secondary Pump :
Sections
|
Flow
|
Velocity
|
Pipe Size Diameter
|
Friction Loss
|
Suction
Side
|
TR
x 2.4
102x2.4=244.8Gallons/Min
(15.4 Litres/Sec)
|
4
to 7
6
Feet/Sec
(1.82metres/Sec)
|
4
Inch
(101.6mm)
|
2.7
Inches of Water Gauge/100Ft
(22.13
Pascals/Metre)
|
Discharge
Side
|
TR
x 2.4
102x2.4=244.8Gallons/Min
(15.4 Litres/Sec)
|
8-12
10
(3.04metres/Sec)
|
3
Inch
(
72.15mm)
|
10.1
Inches of Water Gauge/100Ft
(82.8)Pascals/Metre)
|
Calculation for Condenser Piping (Open Piping
System)
Primary Pump :
Sections
|
Flow
|
Velocity
|
Pipe Size Diameter
|
Friction Loss
|
Suction
Side
|
TR
x 3.0
102x3.0=306
Gallons/Min
(19.3Litres/Sec)
|
4
to 7
6
Feet/Sec
(1.82metres/Sec)
|
5
Inch
(127mm)
|
4.5
Inches of Water Gauge/100Ft
(
36.89Pascals/Metre)
|
Discharge
Side
|
TR
x 3.0
102x3.0=306
Gallons/Min
(19.3Litres/Sec)
|
8-12
10
(3.04metres/Sec)
|
3.5
Inch
(88.9
mm)
|
15
(122.9Pascals/Metre)
|
Secondary Pump :
Sections
|
Flow
|
Velocity
|
Pipe Size Diameter
|
Friction Loss
|
Suction
Side
|
TR
x 3.0
102x3.0=306
Gallons/Min
(19.3Litres/Sec)
|
4
to 7
6
Feet/Sec
(1.82metres/Sec)
|
5
Inch
(127mm)
|
4.5
Inches of Water Gauge/100Ft
(
36.89Pascals/Metre)
|
Discharge
Side
|
TR
x 3.0
102x3.0=306
Gallons/Min
(19.3Litres/Sec)
|
8-12
10
(3.04metres/Sec)
|
3.5
Inch
(88.9
mm)
|
15
(122.9Pascals/Metre)
|
Click Below Link To Download The Word File